BASgatewayLX


C
O
N
TR LSO
®
CONTEMPORARY
BASgatewayLX


Modbus remains a popular network interface. It is commonly used with boiler control,
variable speed drives, and metering applications but these devices lack BACnet
compliance. To make Modbus devices appear as individual BACnet devices, the
BASgatewayLX is used. This device has one 10/100 Mbps Modbus TCP or BACnet/
IP Ethernet port and an opto-isolated Modbus EIA-485 serial port for Modbus RTU or
Modbus ASCII devices.
Up to 30 Modbus serial devices can share the unit’s Modbus port and up to 1000
Modbus registers can be processed. The virtual routing feature in the BASgatewayLX
allows each connected Modbus device to appear as an individual BACnet-compliant
device. What is needed is a device prole for each Modbus type device. Contemporary
Controls maintains a library of common device proles. If one is not available,
Contemporary Controls will provide it upon request. Custom device proles can be
uploaded to the gateway.
Using web pages and a resident database of common Modbus device proles, Modbus
registers from Modbus Serial devices can be mapped to BACnet objects.
Gateway Functionality Between …
Modbus Serial (RTU or ASCII) to BACnet/IP
Modbus TCP and BACnet/IP
Routing Functionality Between…
Modbus Serial (RTU and ASCII) and Modbus TCP
Flexible Communication Ports
10/100 Mbps Ethernet with auto-negotiation and Auto-MDIX
Opto-isolated serial port supports either 2-wire or 3-wire EIA-485
Jumper-selectable EIA-485 bias and termination
Baud rates from 2.4–115.2 kbps
Convenient Installation
24 VAC/VDC powered
DIN-rail mounting
Seitenansicht 0
1 2 3 4 5 6 ... 15 16

Inhaltsverzeichnis

Seite 1 - BASgatewayLX

BASgatewayLXCONTR LSO®CONTEMPORARYBASgatewayLXModbus remains a popular network interface. It

Seite 2 - Copyright

 If using shielded cable, connect to chassis at only one point. Wire size may be dictated by electrical codes for the area

Seite 3 - 

EIA-485 Bias and Termination JumpersAfter removing the gateway cover, three jumpers are accessible on a 6-pin jumper block located near

Seite 4

Each BASgatewayLX contains an interactive web server, accessible from any Internet-compatible PC on the local netwo

Seite 5 - Mechanical

On some systems, this option is: “My Network Places”.Figure 13 — Steps for Changing the IP Address of the PC Used for Setup

Seite 6

After entering the BASgatewayLX’s IP address into your browser’s address eld, you will see a Logon Screen prompting for the Use

Seite 7

The product features embedded help which can be useful during installation. More information can

Seite 8

[This page was left blank intentionally.]

Seite 9 - 

TrademarksContemporary Controls, ARC Control, ARC DETECT, BASautomation, EXTEND-A-BUS, RapidRing, and CTRLink are trademarks or re

Seite 10 - 

Electrical (± 10%)Input voltage: 24 V 24 VInput power: 6 W 10 VAInput frequency: N/A 47–63 Hz (Intended for use with

Seite 11

EnvironmentalOperating temperature: 0°C to +60°CStorage temperature: –40°C to +85°CHumidity: 10% to 95%, non-condensingEthernet Co

Seite 12 - 

MechanicalFigure 5 — Dimensional Drawing

Seite 13 - 

The BASgatewayLX requires 24 VAC or 24 VDC and draws a commensurate amount of current. The recommended conductor size is 16–18 AWG.

Seite 14

For devices that share a power source with our product, see Figure 5 for proper 2-wire bus connections and Figure 6 for proper 3-wire bus

Seite 15 - 

For devices that do not share power with our product, see Figure 7 for proper 2-wire bus connections and Figure 8 for proper 3-wire bus c

Seite 16

Limited Power SourcesThe gateway should be powered by a limited power source complying with the requirements of the National